We intend to upgrade a PLC5 control system to ControlLogix. It is our intention to use the existing PLC5 I/O by removing the 5/25 processor and replacing with a 1771-ASB and connectiong via RIO to a 1756-DHRIO card in the new ControlLogix chassis. WWW_PL※CJS_COM-PLC-技.术_网
Setting this up looks reasonably straight forward to talk to the Digital I/O, however we are a little unsure as to how to approach the Analogs. Has anybody done this before and if so your help would be appreciated. WWW_PLC※JS_COM-PmLC-技.术_网
plcjs.技.术_网
I have done a few PLC5 , PLC5/250, and PLC 3 conversions to Contrologix. The 1771 analogs are treated the same with BTR and BTW instructions except using the MSG instruction, which has the Block Transfer Reads and Writes as a message type. W1WW_P4LCJS_COM-PLC-技.术_网
WW.W_PLC※JS_C,OM-PL,C-技.术_网
Another option would be to go Controlnet, but I realize the RIO blue hose is already in place.